The tank safety valve shall operate by means of hydraulic pressure from the transfer pump discharge. The valve shall open on positive pressure and close on loss of pressure. It shall be equipped to relieve downstream to upstream in the event of thermal buildup. It shall be equipped with a manual opening feature and valve position indicator.
The OCV 66TS Tank Safety Valve is designed to automatically isolate a fuel storage tank from its loading terminal or product transfer point. Hydraulically linked to the delivery pump, the valve is open only when the pump runs and is effectively producing pressure. The valve will automatically close when the pump is off, fails to produce pressure, or in the event of a line rupture.
Size Unit
Size range
Pressure rating
Pressure Rating (ANSI at 100°)
250psi for Class 150# ANSI Flanged Ductile Iron
285psi for Steel/Stainless Steel & Aluminum
300# ANSI Flanges are available
End connection type
Sizes
Threaded Ends: 2″ – 3″
Grooved Ends: 2″ – 6″ (globe) 2″ – 4″ (angle)
Flanged Ends: 2″ – 16″ (globe & angle)
Materials of construction
Body and Cover
Ductile Iron
Carbon Steel
Stainless Steel
Aluminum
Trim Material
Stainless Steel
Optional Components
Two-Stage Opening
Pre-Wired Junction Box