Fueling

OCV 114-2 Aviation

Hydrant Control Valve

The hydrant control valve shall function to reduce a higher upstream pressure to a constant, lower downstream pressure regardless of fluctuations in supply or demand. The valve shall be equipped with a two-way hydraulic valve that will allow the valve to open when pressurized, and is also equipped with a high capacity surge control pilot to close the valve quickly in the event of sudden reduction in flow. It shall also be equipped with a rate of flow control pilot that will automatically limit the maximum flow rate. Sensing of the pilot shall be by means of a calibrated orifice plate integrally installed in the upstream valve flange. The valve will open automatically in the event of pressure reversal. The OCV 114-2 is a control valve specifically designed for aircraft refueling service. Known as either a refueling or a hydrant control valve, it is the typical control valve used on pantograph refueling systems. It performs the following functions:
– Opens and closes electrically via hydraulic deadman control
– While open, modulates to control downstream pressure at a predetermined set point
– Closes rapidly to prevent undue pressure buildup due to a rapid reduction in demand
– Limits flow rate to a predetermined maximum

Downloads

Product Page (PDF)

IOM (PDF)

Technical Specifications

Size Unit

Size range

DN32 - DN600 (1¼” - 24")

Pressure rating

Pressure Rating (ANSI at 100°)

250psi for Class 150# ANSI Flanged Ductile Iron

285psi for Steel/Stainless Steel & Aluminum

300# ANSI Flanges are available

End connection type

Sizes

Threaded Ends: 1¼” – 3″

Grooved Ends: 1½” – 6″ (globe & angle)

Flanged Ends: 1¼” – 24″ (globe); 1¼” – 16″ (angle)

 

Materials of construction

Body and Cover

Ductile Iron

Carbon Steel

Stainless Steel

Aluminum

Trim Material

Stainless Steel

Optional Components

Two-Stage Opening

Visual Indicator

Pre-Wired Junction Box

Features & Benefits

Pressure reducing pilot
  • Senses valve outlet or pressure compensating venturi
High-capacity surge control
  • Minimizes pressure buildup on reduction of flow
Hydraulic deadman control
  • Electrically opens & closes
Rate of flow pilot
  • Limits maximum flow
Wide range of certifications
  • ABS Type Approval; CE (Conformité Européenne) Compliance; UFGS Guide Specifications & more