The hydrant control valve shall function to reduce a higher upstream pressure to a constant, lower downstream pressure regardless of fluctuations in supply or demand. The valve shall be equipped with a two-way hydraulic valve that will allow the valve to open when pressurized, and is also equipped with a high capacity surge control pilot to close the valve quickly in the event of sudden reduction in flow. It shall also be equipped with a rate of flow control pilot that will automatically limit the maximum flow rate. Sensing of the pilot shall be by means of a calibrated orifice plate integrally installed in the upstream valve flange. The valve will open automatically in the event of pressure reversal. The OCV 114-2 is a control valve specifically designed for aircraft refueling service. Known as either a refueling or a hydrant control valve, it is the typical control valve used on pantograph refueling systems. It performs the following functions:
– Opens and closes electrically via hydraulic deadman control
– While open, modulates to control downstream pressure at a predetermined set point
– Closes rapidly to prevent undue pressure buildup due to a rapid reduction in demand
– Limits flow rate to a predetermined maximum
Size Unit
Size range
Pressure rating
Pressure Rating (ANSI at 100°)
250psi for Class 150# ANSI Flanged Ductile Iron
285psi for Steel/Stainless Steel & Aluminum
300# ANSI Flanges are available
End connection type
Sizes
Threaded Ends: 1¼” – 3″
Grooved Ends: 1½” – 6″ (globe & angle)
Flanged Ends: 1¼” – 24″ (globe); 1¼” – 16″ (angle)
Materials of construction
Body and Cover
Ductile Iron
Carbon Steel
Stainless Steel
Aluminum
Trim Material
Stainless Steel
Optional Components
Two-Stage Opening
Visual Indicator
Pre-Wired Junction Box