Fueling

OCV 110-29 Terminal

Two-Stage Differential Control Valve

The two-stage differential control valve shall open in one stage and close in two stages based on signals from the preset register. Additionally, in liquid fuel systems, the valve will close as necessary when air is sensed in the air eliminator so as to prevent air from passing through the meter. In LPG systems, the valve will modulate as necessary to keep the valve inlet pressure (meter outlet pressure) a predetermined amount above vapor pressure to ensure that only liquid passes through the meter. The OCV 110-29 is specifically designed for fuel loading systems and performs the following functions:
– Full flow delivery with two stage shutdown
– In liquid fuel systems, prevents air from passing through meter
– In LPG systems, prevents flashing through meter

Downloads

Product Page (PDF)

IOM (PDF)

Technical Specifications

Size Unit

Size range

DN32 - DN600 (1¼” - 24")

Pressure rating

Pressure Rating (ANSI at 100°)

250psi for Class 150# ANSI Flanged Ductile Iron

285psi for Steel/Stainless Steel & Aluminum

300# ANSI Flanges are available

End connection type

Sizes

Threaded Ends: 1¼” – 3″

Grooved Ends: 1½” – 6″ (globe & angle)

Flanged Ends: 1¼” – 24″ (globe); 1¼” – 16″ (angle)

 

Materials of construction

Body and Cover

Ductile Iron

Carbon Steel

Stainless Steel

Aluminum

Trim Material

Stainless Steel

Optional Components

Two-Stage Opening

Visual Indicator

Pre-Wired Junction Box

Features & Benefits

Preset Register
  • Sends signal to open in one stage
  • Sends signals to close in two stages (mechanical & electronic)
Differential control valve
  • Full flow delivery with two-stage shutdown
  • In liquid fuel systems, prevents air from passing through meter
  • In LPG systems, prevents flashing through meter
Can be maintained without removal from the line
  • Easy maintenance
Factory tested
  • Quick & easy installation
Wide range of certifications
  • ABS Type Approval; PED; TSSA; American-Made & more